Section 114.235. Sag-related clearances.  


Latest version.
  • [Follows NESC 235C2b(1)(a) Exception 2, p. 150] (Change) Change Exception 2 to read:
    Exception 2: For supply conductors of different utilities, vertical clearance at any point in the span need not exceed 75% of the values required at the supports for the same utility by Table 235-5.