Wisconsin Administrative Code (Last Updated: January 10, 2017) |
Agency PSC. Public Service Commission |
Chapter 114. Wisconsin State Electrical Code, Volume 1 |
SubChapter III. Omissions, Changes or Additions to NESC-2012 |
Part 2. Safety Rules for the Installation and Maintenance of Overhead Electric Supply and Communication Lines |
Section 114.235. Sag-related clearances.
Latest version.
- [Follows NESC 235C2b(1)(a) Exception 2, p. 150] (Change) Change Exception 2 to read:Exception 2: For supply conductors of different utilities, vertical clearance at any point in the span need not exceed 75% of the values required at the supports for the same utility by Table 235-5.
CR 07-021
: cr.
Register January 2008 No. 625
, eff. 2-1-08;
CR 13-039
: r. and recr.
Register June 2014 No. 702
, eff. 7-1-14; renum. PSC 114.235 from PSC 114.235C2b(1)(a) under s.
13.92 (4) (b) 1.
, Stats.,
Register March 2015 No. 711
.