Section 362.1021. Exits from stories.  


Latest version.
  • (1)  Substitute the following wording for the requirements in IBC section 1021.1: All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1021.1 based on the occupant load of the story. For the purposes of this chapter, occupied roof shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrival at grade or the public way.
    (2)  This is a department exception to the requirements in IBC section 1021.1: Buildings of Group I-3 occupancy that are used as guard towers, provided the towers are no higher than 2 stories above grade, accommodate no more than 10 occupants, and have a travel distance of no more than 75 feet.
CR 06-120 : cr. Register February 2008 No. 626 , eff. 3-1-08; correction made to (2) (a), (b) and (c) under s. 13.92 (4) (b) 7. , Stats., Register February 2008 No. 626 , eff. 3-1-08; CR 10-103 : renum. from Comm 62.1019 and am. (title), (1), cr. (2) Register August 2011 No. 668 , eff. 9-1-11.