Section 341.41. Installation registration.  


Latest version.
  • (1) Boiler or pressure vessel installation registration.
    (a) Except as provided in par. (b) , the installation of any boiler or pressure vessel shall be registered with the department by the installer before the operation of the boiler or pressure vessel. Registration shall be on form SBD-6314-E.
    (b) Registration with the department is not required for any of the following:
    1. Boilers and pressure vessels exempted from periodic inspections in s. SPS 341.18 .
    2. Installations in cities of the first class if an installation registration form has been filed with the appropriate city official.
    (2) Power piping installation registration.
    (a) Except as provided in par. (b) , the installation of any power piping system shall be registered with the department by the installer before the operation of the piping system. Registration shall be on form SBD-5204-E.
    (b) Registration is not required for any of the following:
    1. Power piping of 2 inches nominal pipe size and smaller.
    2. Installations in cities of the first class if an installation registration form has been filed with the appropriate city official.
    3. Underground power piping systems that are not located in a walk-in tunnel.
    4. Power piping replacements, modifications and alterations to existing systems and for new installations, any of which do not exceed 50 feet in length.
    5. Installations at one- or 2-family dwellings.
    (3) Piping on single power boilers. ASME form P-4B is not required to be completed for boiler piping on any single ASME "S", "M" or "E" stamped boiler rated at 50 boiler horsepower or less and 150 psig or less maximum allowable working pressure, if applicable pressure and temperature rated valves and at least schedule 80 pipe and fittings are used.
    (4) Installation registration for solid-fuel-fired water-heating appliances.
    (a) Except as specified in par. (b) , the installer of a solid-fuel-fired water-heating appliance shall register the unit with the department and shall use department form SBD-6314-E for the registration.
    (b) Registration of a solid-fuel-fired water-heating appliance installed at a one- or 2-family dwelling is not required.
Cr. Register, February, 1988, No. 386 , eff. 3-1-88; am. (1) (a) and (2) (a), Register, December, 1992, No. 444 , eff. 1-1-93; CR 05-025 : am. (2) (b), cr. (3) Register October 2005 No. 598 , eff. 11-1-05; CR 08-028 : cr. (2) (b) 5., (c) and (4) Register November 2008 No. 635 , eff. 12-1-08; correction in (1) (b) 1. made under s. 13.92 (4) (b) 7. , Stats., Register December 2011 No. 672 ; CR 11-047 : am. (1) (a), (b) (intro.), 1., (2) (a), renum. (2) (c) to be (2) (b) 5. (note) and am., am. (4) (b) Register May 2012 No. 677 , eff. 6-1-12.

Note

The Department forms required in this chapter are available for a nominal fee at telephone 800-DOC-SALE or 411 (Telecommunications Relay), or at docsales@doa.state.wi.us , or at no charge at the Department's Web site at www.dsps.wi.gov through links to Division of Industry Services forms. Microsoft Windows NT 6.1.7601 Service Pack 1 The Department forms required in this chapter are available for a nominal fee at telephone 800-DOC-SALE or 411 (Telecommunications Relay), or at docsales@doa.state.wi.us , or at no charge at the Department's Web site at www.dsps.wi.gov through links to Division of Industry Services forms. Microsoft Windows NT 6.1.7601 Service Pack 1 Section SPS 341.16 (2) (c) requires the piping installer to notify the Department or authorized agent or a certified inspector at least 5 business days prior to the installation to schedule an inspection. Microsoft Windows NT 6.1.7601 Service Pack 1 The Department forms required in this chapter are available for a nominal fee at telephone 800-DOC-SALE or 411 (Telecommunications Relay), or at docsales@doa.state.wi.us , or at no charge at the Department's Web site at www.dsps.wi.gov through links to Division of Industry Services forms. Microsoft Windows NT 6.1.7601 Service Pack 1