Wisconsin Administrative Code (Last Updated: January 10, 2017) |
Agency SPS. Department of Safety and Professional Services |
Chapters 301-. Safety, Buildings, and Environment |
Chapters SPS326-360. General, Part II |
Chapter SPS341. Boilers And Pressure Vessels |
SubChapter III. All Installations |
Section 341.35. Interconnected boilers.
Latest version.
- When boilers of different maximum allowable working pressures with minimum safety valve settings varying more than 6% are so connected that steam can flow toward the lower pressure units, the latter shall be protected by additional safety valve capacity, if necessary, on the lower pressure side of the system. The additional safety valve capacity shall be based upon the maximum amount of steam that can flow into the lower pressure system. The additional safety valves shall have at least one valve set at a pressure not to exceed the lowest allowable pressure and the other valves shall be set within a range not to exceed 3% above that pressure.
History: Cr.
Register, February, 1988, No. 386
, eff. 3-1-88;
CR 11-047
: am.
Register May 2012 No. 677
, eff. 6-1-12.