Wisconsin Administrative Code (Last Updated: January 10, 2017) |
Agency SPS. Department of Safety and Professional Services |
Chapters 301-. Safety, Buildings, and Environment |
Chapters SPS320-325. Uniform Dwelling Code |
Chapter SPS323. Heating, Ventilating And Air Conditioning |
SubChapter IV. Delivery Systems |
Section 323.09. Dampers, registers and grilles.
Latest version.
- (1) Volume and backdraft dampers.(a) Volume duct dampers shall be provided to permit balancing of the system.(b) Volume dampers shall be provided with access.(c) Supply ducts may not terminate in a garage unless a backdraft damper is provided.(2) Air registers and grilles.(a) Supply air registers. All supply air outlets shall be provided with registers or devices which will provide a uniform distribution of air.(b) Return air grilles. Return air grilles shall not be located in bathrooms, kitchens, garages, utility spaces or a confined space in which a draft diverter or draft regulator is located. All other habitable spaces shall have permanent openings to a return air grille equal in area to the supply outlet serving those areas. At least one return air opening shall be provided for each floor.
History:
Cr.
Register, November, 1979, No. 287
, eff. 6-1-80;
CR 08-043
: renum. (1) to (1) (a), cr. (1) (b)
Register March 2009 No. 639
, eff. 4-1-09.
Note
Acceptable means of access include a manufactured access panel, an air grille used as a cover, a plastic ceiling cap or a damper accessible through an air diffuser or grille.