Section 323.07. Air distribution systems.  


Latest version.
  • (1) Sizing. All air distribution systems shall be sized using the velocities and static pressure losses listed in Table 323.07.
    (2) System sizing. The distribution system, including the evaporator coil, air filters (installed external to the heating unit), ducts, fittings, grilles and registers, shall be sized so that the total external static pressure shall not exceed the static pressure capacity of the fan at the system rated air flow.
    (3) Changes in duct size. Where duct sizes are changed, the slope angle of the transition duct shall not exceed 45 ° .