Wisconsin Administrative Code (Last Updated: January 10, 2017) |
Agency SPS. Department of Safety and Professional Services |
Chapters 301-. Safety, Buildings, and Environment |
Chapters SPS320-325. Uniform Dwelling Code |
Chapter SPS323. Heating, Ventilating And Air Conditioning |
SubChapter III. Heating Equipment |
Section 323.06. Combustion air.
Latest version.
- (1) Scope.(a) Naturally vented appliances and other appliances that require air for combustion and dilution of flue gases to be taken from within the building shall comply with this section.(b) Appliances that are provided with a direct supply of outside air for combustion in accordance with the manufacturer's installation instructions and listing are not required to comply with this section.(c) Where the appliance listing and manufacturer's instructions are more stringent than the provisions of this section, the listing and manufacturer's instructions apply.(d) Listed fireplace stoves are not required to comply with this section if permitted in the manufacturer's instructions.(e) Masonry fireplaces shall conform to the requirements of s. SPS 321.29 .(f) Listed factory-built fireplaces shall comply with the manufacturer's recommendations and shall conform with the requirements of s. SPS 321.32 .(2) Methods for providing air. Air for combustion and dilution shall be provided in accordance with one of the following:(a) If the vapor retarder is not continuous on walls and ceilings exposed to the outside atmosphere as allowed by s. SPS 322.38 , air may be provided from inside the building in accordance with sub. (3) .(b) Air may be provided from outside the building in accordance with sub. (4) .(c) The appliance may be installed in accordance with its listing and manufacturer's instructions. Where all walls and ceilings exposed to the outside atmosphere are provided with a continuous vapor retarder, any requirements for unusually tight construction shall be met.(d) An engineered system providing an adequate supply of air for combustion ventilation and dilution of flue gases may be installed if approved by the department.(3) Air from inside the building.(a)1. The equipment shall be located in a space with a volume not less than 50 cubic feet per 1000 Btu/h of the combined input rating of all fuel-burning appliances drawing combustion and dilution air from that space.2. The space may be made up of more than one room if the rooms are connected through doorways without doors or connected through sets of openings described in par. (b) .(b)1. When needed to connect rooms, two openings shall be provided, one within one foot of the ceiling of the room and one within one foot of the floor.2. The net free area of openings shall be calculated in accordance with sub. (5) .3. The net free area of each opening shall be a minimum of one square inch per 1000 Btu/h of combined input rating of the fuel burning appliances drawing combustion and dilution air from the communicating rooms, but shall be not less than 100 square inches.(4) Air from outside the building.(a) When air for combustion and dilution is provided from outside the building, as allowed under sub. (2) (b) , one of the methods specified in pars. (b) to (d) shall be used.(b) Openings may be provided to connect rooms containing appliances to the outdoors.1.a. Two openings shall be provided, one within one foot of the ceiling of the room and one within one foot of the floor.b. Openings may connect directly to the outdoors or to the outdoors through a horizontal or vertical duct.c. The net free area of openings shall be calculated in accordance with sub. (5) .2. The net free area of each direct opening to the outdoors not using a duct shall be a minimum of one square inch per 4000 Btu/h of combined input rating of the fuel-burning appliances drawing combustion and dilution air from the room.3.a. The net free area of each opening connected to the outdoors through a horizontal duct shall be a minimum of one square inch per 2000 Btu/h of combined input rating of the fuel-burning appliances drawing combustion and dilution air from the room.b. The cross-sectional area of the duct shall be equal to or greater than the required size of the opening.4.a. The net free area of each opening connected to the outdoors through a vertical duct shall be a minimum of one square inch per 4000 Btu/h of combined input rating of the fuel-burning appliances drawing combustion and dilution air from the room.b. The cross-sectional area of the duct shall be equal to or greater than the required size of the opening.(c)1. Where all appliances drawing air for combustion and dilution from the room are gas appliances, air may be provided via a single opening to connect the room to the outdoors in accordance with this paragraph.2.a. The opening shall be located within one foot of the ceiling of the room.b. The opening may connect directly to the outdoors, may connect to the outdoors through a horizontal duct, or may connect to the outdoors through a vertical duct.c. The net free area of the opening shall be calculated in accordance with sub. (5) .3.a. The net free area of the opening shall be a minimum of one square inch per 3000 Btu/h of combined input rating of the fuel-burning appliances drawing combustion and dilution air from the room, and not less than the combined cross-sectional flow areas of the appliance flue collars or draft hood outlets.b. The cross-sectional area of the duct shall be equal to or greater than the required size of the opening.4. The appliances shall have a minimum clearance to the surfaces of the room of one inch at the sides and back of the appliance and 6 inches at the front of the appliance.(d)1. A combination of openings to the outside and openings to other rooms may be used in accordance with this paragraph.2.a. One opening shall connect directly to the outdoors, connect to the outdoors through a horizontal duct, or connect to the outdoors through a vertical duct.b. The net free area of the openings shall be calculated in accordance with sub. (5) .c. The net free area of the opening shall be a minimum of one square inch per 5000 Btu/h of combined input rating of the fuel burning appliances drawing combustion and dilution air from the room.d. The cross-sectional area of a duct, if used, shall be equal to or greater than the required size of the opening.3.a. The equipment shall be located in a space with a volume not less than 50 cubic feet per 1000 Btu/h of the combined input rating of all fuel-burning appliances installed in that space.b. The space may be made up of more than one room if the rooms are connected through openings without doors or connected through sets of openings described in subd. 4.4.a. When needed to connect rooms, two openings shall be provided, one within one foot of the ceiling of the room and one within one foot of the floor.b. The net free area of openings shall be calculated in accordance with sub. (5) .c. The net free area of each opening shall be a minimum of one square inch per 1000 Btu/h of combined input rating of the fuel burning appliances drawing combustion and dilution air from the communicating rooms, but shall be not less than 100 square inches.(5) Net free area calculation.(a) The required size of openings for combustion and dilution air shall be based on the net free area of each opening.(b) The net free area of an opening shall be that specified by the manufacturer of the opening covering or by a source approved by the department.(c) In the absence of such information, openings covered with metal louvers shall be deemed to have a net free area of 75 percent of the area of the opening, and openings covered with wood louvers shall be deemed to have a net free area of 25 percent of the area of the opening.(6) Interlocking of dampers.(a) Where the combustion air openings are provided with volume, smoke or fire dampers, the dampers shall be electronically interlocked with the firing cycle of the appliances served, so as to prevent operation of any appliance that draws combustion and dilution air from the room when any of the dampers are closed.(b) Manually operated dampers shall not be installed in combustion air openings.(7) Simultaneous operation.(a) The equipment and appliance within every room containing fuel-burning appliances shall be installed so as to allow the free circulation of air.(b) Provisions shall be made to allow for the simultaneous operation of mechanical exhaust systems, fireplaces, clothes dryers or other equipment and appliances operating in the same room or space from which combustion air and dilution air is being drawn. The provisions shall prevent the operation of the appliances, equipment and systems from affecting the supply of combustion and dilution air.
History:
Cr.
Register, November, 1979, No. 287
, eff. 6-1-80; am. (intro.), (1) (a) and (2) (a),
Register, January, 1989, No. 397
, eff. 2-1-89; r. and recr.
Register, March, 2001, No. 543
, eff. 4-1-01
;
correction in (2) (a) made under s.
13.92 (4) (b) 7.
, Stats.,
Register March 2009 No. 639
; correction (2) (a) made under s.
13.92 (4) (b) 7.
, Stats.,
Register December 2011 No. 672
;
CR 15-041
: cr. (1) (d) to (f)
Register December 2015 No. 720
, eff. 1-1-16.
Note
Wood typically has a heating value of 8600 BTU per pound.
Microsoft Windows NT 6.1.7601 Service Pack 1