Wisconsin Administrative Code (Last Updated: January 10, 2017) |
Agency SPS. Department of Safety and Professional Services |
Chapters 301-. Safety, Buildings, and Environment |
Chapters SPS319. General, Part I |
Chapter SPS316. Electrical |
SubChapter III. Changes, Additions or Omissions to the NEC ® |
Section 316.701. Legally required standby systems.
Latest version.
- (1) Addition. This is a department rule in addition to the requirements in NEC 701.12 (intro.): The enclosure of the alternate source of power located outdoors for legally required standby systems shall be located at least 10 feet horizontally from any combustible portion of a Type III, Type IV, or Type V building and at least 20 feet from an outdoor electrical transformer, electrical metering, service equipment or normal power distribution equipment. These dimensions may be reduced where a noncombustible barrier is installed that extends at least 3 feet beyond each side of the alternate power source and transformer. The height of the barrier shall be at least one foot above the top of the transformer, electrical metering, service equipment, or alternate power source, whichever is higher.(2) Deletion. The requirements specified in NEC 701.12 (B) (3) are not included as part of this chapter.
CR 08-047
: cr.
Register February 2009 No. 638
, eff. 3-1-09; correction in (1) made under s.
13.92 (4) (b) 7.
, Stats.,
Register February 2009 No. 638
; corrections in (1), (2) made under s.
13.92 (4) (b) 7.
, Stats.,
Register November 2013 No. 695
.