Section 812.35. Yard hydrants.  


Latest version.
  • Yard hydrants may be installed in a water system provided they are not installed in or on a well and have been approved by the department of safety and professional services for this purpose. All backflow prevention devices shall comply with ch. SPS 384 and shall be installed and maintained in accordance with ch. SPS 382 .
    (1)  Yard hydrants having hose threaded outlets shall either:
    (a) Have a hose connection vacuum breaker installed on the hose threads, or
    (b) Have a reduced pressure principle backflow preventer or a backflow preventer with intermediate atmospheric vent installed in the water supply pipe which serves only the yard hydrant or hydrants.
    - See PDF for diagram PDF Figure 40. Required watertight concrete pump platform for hand pumps installed outside. The platform shall be mounded
    so water does not accumulate around the well casing.
    - See PDF for diagram PDF Figure 41. Overflow piping arrangement for a flowing well with a submersible pump.
    - See PDF for diagram PDF Figure 42. Flowing well installation with a surge tank instead of an overflow piping arrangement.
    (2)  Yard hydrants without hose threaded outlets may be installed without additional backflow protection if the outlet of the yard hydrants complies with the air gap requirements in s. SPS 382.41 .
History: Cr. Register, January, 1991, No. 421 , eff. 2-1-91; correction in (intro.) made under s. 13.93 (2m) (b) 12., Stats., Register, September, No. 465 ; corrections made under s. 13.93 (2m) (b) 4., Stats., Register, September, 1996, No. 489 ; correction in (intro.) made under s. 13.93 (2m) (b) 7., Stats, Register, May, 2000, No. 533 ; correction in (intro.), (3) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672 ; CR 13-099 : am. (intro.), r. (1), renum. (2), (3) to (1), (2) and am. Register September 2014 No. 705 , eff. 10-1-14; CR 13-099 transcription error in (2) corrected Register Otober 2016 No. 730.

Note

Chapter SPS 384 requires that backflow prevention devices such as hose connection vacuum breakers, backflow preventers with intermediate atmospheric vent and reduced pressure principle backflow preventers must be reviewed by and receive device approval from department of safety and professional services. Chapter SPS 382 requirements do not allow backflow preventers to be buried or installed in a pit. Installation of hose connection vacuum breakers in areas subject to freezing must be of the type that allows draining. Department of safety and professional services plan approval must be received prior to the installation of a reduced pressure principle backflow preventer. Reduced pressure principle backflow preventers must be installed by a plumber licensed under ch. 145 , Stats. and listed by department of safety and professional services to do such work. The device must be tested at least once a year by a department of safety and professional services listed backflow prevention device tester. Microsoft Windows NT 6.1.7601 Service Pack 1 As the result of an incorrect transcription of the amendment of sub. (2) by CR 13-099 , that provision incorrectly read “Yard hydrants having hose threaded outlets...” from 10-1-14 to 11-1-16. Microsoft Windows NT 6.1.7601 Service Pack 1