Wisconsin Administrative Code (Last Updated: January 10, 2017) |
Agency SPS. Department of Safety and Professional Services |
Chapters 301-. Safety, Buildings, and Environment |
Chapters SPS319. General, Part I |
Chapter SPS316. Electrical |
SubChapter III. Changes, Additions or Omissions to the NEC ® |
Section 316.314. Outlet, device, pull and junction boxes; conduit bodies; fittings; and handhole enclosures.
Latest version.
- (1) Conductors entering boxes, conduit bodies, or fittings. This is a department exception to the requirements of NEC 314.17 (B) and (C):Exception: Nonmetallic sheathed cable is not required to be secured to the box or conduit body where it is installed in accordance with the wiring method specified in s. SPS 316.312 .(2) Outlet boxes. This is a department rule in addition to the requirements of NEC 314.27 (A): In a dwelling unit, a ceiling outlet box installed for use as a lighting fixture outlet in a habitable room or kitchen and located where a ceiling fan could be installed shall be a type listed for ceiling fan support.
CR 08-047
: cr.
Register February 2009 No. 638
, eff. 3-1-09; correction in (1) made under s.
13.92 (4) (b) 7.
, Stats.,
Register December 2011 No. 672
;
CR 13-042
: am. (title)
Register November 2013 No. 695
, eff. 12-1-13.