Section 316.314. Outlet, device, pull and junction boxes; conduit bodies; fittings; and handhole enclosures.  


Latest version.
  • (1) Conductors entering boxes, conduit bodies, or fittings. This is a department exception to the requirements of NEC 314.17 (B) and (C):
    Exception: Nonmetallic sheathed cable is not required to be secured to the box or conduit body where it is installed in accordance with the wiring method specified in s. SPS 316.312 .
    (2) Outlet boxes. This is a department rule in addition to the requirements of NEC 314.27 (A): In a dwelling unit, a ceiling outlet box installed for use as a lighting fixture outlet in a habitable room or kitchen and located where a ceiling fan could be installed shall be a type listed for ceiling fan support.
CR 08-047 : cr. Register February 2009 No. 638 , eff. 3-1-09; correction in (1) made under s. 13.92 (4) (b) 7. , Stats., Register December 2011 No. 672 ; CR 13-042 : am. (title) Register November 2013 No. 695 , eff. 12-1-13.