Section 316.312. Cabinets, cutout boxes and meter socket enclosures.
Latest version.
- (1) Cables. Substitute the following wording for NEC 312.5 (C) Exception (intro.):Exception: Cables with entirely nonmetallic sheaths may enter an enclosure through one or more nonflexible raceways of not less than 12 inches and not more than 10 feet in length, provided all of the following conditions are met:(2) Omission. The requirements specified in NEC 312.5 (C) Exception paragraph (b) are not included as part of this chapter.(3) Fitting . Substitute the following wording for NEC 312.5 (C) Exception paragraph (c): A fitting is provided on each end of the raceway to protect the cable from abrasion.
CR 08-047
: cr.
Register February 2009 No. 638
, eff. 3-1-09.