Wisconsin Administrative Code (Last Updated: January 10, 2017) |
Agency PSC. Public Service Commission |
Chapter 114. Wisconsin State Electrical Code, Volume 1 |
SubChapter III. Omissions, Changes or Additions to NESC-2012 |
Part 3. Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines |
Section 114.381. Warning signs.
Latest version.
- [Follows NESC 381G, p. 257] (Addition) Add paragraph H to read:H. Warning signs1. Where a padmounted transformer, switchgear, pedestal, or similar above-grade enclosure is not within a fenced or other protected area and contains live parts in excess of 600 volts, a permanent and conspicuous warning sign shall be provided on the outside of the enclosure which meets the requirements as to format and color of American National Standards Institute standard ANSI Z535.1-2011, ANSI Z535.2-2011, ANSI Z535.3-2011, ANSI Z535.4-2011, and ANSI Z535.5-2011 for safety signs.2. Electric supply equipment installed prior to July 1, 2003 shall be signed to comply with these rules or the rule in effect in 2003. Warning signs installed as replacements or installed on new facilities shall comply with the standard as prescribed in s. PSC 114.381 H1 above. The "Mr. Ouch" symbol may be used as the optional pictorial part of this sign.
CR 07-021
: cr.
Register January 2008 No. 625
, eff. 2-1-08;
CR 13-039
: r. and recr.
Register June 2014 No. 702
, eff. 7-1-14; renum. PSC 114.381 from PSC 114.381H under s.
13.92 (4) (b) 1.
, Stats.,
Register March 2015 No. 711
.