Section 346.14. Physical environment.  


Latest version.
  • (1) Juvenile housing.
    (a) Each juvenile shall have a separate bunk or bed in a cell which meets the requirements of sub. (2) or s. DOC 346.15 , or in a dormitory which meets the requirements of sub. (3) . A facility may not exceed its rated bed capacity.
    (b) The total number of juveniles housed in double cells under s. DOC 346.15 and in dormitories under sub. (3) may not exceed 75% of the rated bed capacity of the facility.
    (2) Cells.
    (a) Except if s. DOC 346.15 applies, all cells for juveniles in a facility shall be designated and used for single occupancy only.
    (b) Unless s. DOC 346.15 applies, cells shall have minimum floor area of 35 square feet of unencumbered space. The distance between the floor and ceiling may not be less than 8 feet and the distance between opposite walls may not be less than 6 feet.
    (c) Unless s. DOC 346.15 applies, each cell shall have all of the following:
    1. A rigidly constructed metal bed with the frame bracketed to the wall or bolted to the floor or a bed built in masonry construction of a similar strength.
    2. An unbreakable, institution-type mirror.
    3. A detention strength, metal, institution-type wash basin and toilet. The wash basin and toilet may be combined in one unit. The wash basin shall have hot and cold running water.
    4. A rigidly constructed shelf-type table and seat which are bracketed to the wall or bolted to the floor.
    5. Unless s. DOC 346.15 applies, 2 or more nonremovable, collapsible, detention strength clothing and towel hooks.
    6. Light fixtures of detention strength and providing at least 30 foot candles at 30 inches above the floor. Lights shall have a dimming capability or there shall be a nightlight to allow for comfortable sleeping. There shall be enough illumination for observation of juveniles during security checks.
    (d) There shall be no exposed heating pipes, radiators or controls in cells.
    (e) There shall be a release system designed to unlock cell doors individually and as a group from a single point outside the confinement area.
    (3) Dormitories.
    (a) A juvenile detention facility may use dormitories in addition to cells for the secure detention of juveniles.
    (b) Each dormitory shall be designed for a minimum of 3 and a maximum of 8 juveniles.
    (c) If a juvenile detention facility contains one dormitory, it shall have a minimum of 2 cells designed and used for single occupancy.
    (d) If more than one dormitory is built, the number of dormitory beds may not exceed 50% of the rated bed capacity of the juvenile detention facility.
    (e) If, based on all the criteria under s. DOC 346.10 , a juvenile detention facility determines that placement of a juvenile in a dormitory may jeopardize the health or safety of the juvenile, other juveniles in the facility, staff or the community, the juvenile may not be placed in a dormitory.
    (f) Each dormitory shall have all of the following:
    1. A minimum combined sleeping area and adjacent day room space of 70 square feet per juvenile based on rated bed capacity of the dormitory, excluding toilets, showers and lavatories.
    2. A minimum floor to ceiling height of 8 feet.
    3. Non-locking doors on sleeping rooms, if separate sleeping rooms are provided.
    4. Unrestricted physical access to the day room, lavatories and toilets.
    5. A rigidly constructed metal bed with the frame bracketed to the wall or bolted to the floor for each juvenile based on the rated bed capacity of the dormitory.
    6. For facilities constructed or substantially remodeled after November 1, 2010, all upper bunks equipped with an anti-rollout plate.
    7. Detention strength washbasins and toilets.
    8. Unbreakable, detention strength mirrors sufficient for the number of juveniles confined.
    9. Detention strength tables and seating in the day room based on the rated bed capacity of the dormitory.
    10. Two nonremovable, collapsible, detention strength clothing and towel hooks for each juvenile confined based on the rated bed capacity of the dormitory.
    11. Detention strength light fixtures that provide at least 30 foot candles at 30 inches above the floor. Lights shall have a dimming capability or there shall be a nightlight to allow for comfortable sleeping. There shall be enough illumination for observation of juveniles during security checks.
    (4) Day room.
    (a) Each day room shall have all of the following:
    1. A minimum floor area of 35 square feet for each juvenile based on the rated bed capacity of the adjacent group of cells. In addition, each day room shall have a minimum of 70 square feet of unencumbered space.
    2. Detention strength light fixtures that provide at least 30 foot candles at 30 inches above the floor.
    3. Adequate furnishings and equipment for leisure time activities as required under this chapter.
    4. Detention strength tables and seating based on the rated bed capacity of the adjacent cells.
    (b) There shall be in the day room no exposed heating pipes, radiators or controls which are accessible to juveniles.
    (5) Holding rooms.
    (a) Holding rooms shall be located in an area that allows continuous staff observation or electronic video surveillance of juveniles.
    (b) Each holding room shall have all of the following:
    1. Detention strength, rigidly constructed seats or benches bracketed to the wall or bolted to the floor or seats or benches of masonry construction of similar strength.
    2. A detention strength, metal, institution-type wash basin and toilet.
    3. A minimum floor area of 50 square feet of unencumbered space for 5 or fewer occupants and an additional 10 square feet of unencumbered space for each additional occupant.
    4. Detention strength light fixtures that provide at least 30 foot candles at 30 inches above the floor.
    (c) Holding rooms are not included in the rated capacity of a facility.
    (d) Juveniles may not be held in a holding room for more than 24 continuous hours.
    (e) Holding rooms outside the secure perimeter shall comply with the requirements of this section.
    (6) Receiving cells.
    (a) All receiving cells shall be designed and used for single occupancy.
    (b) Each receiving cell shall have all of the following:
    1. A rigidly constructed metal bed with the frame bracketed to the wall or bolted to the floor or a bed built in masonry construction or similar strength.
    2. A detention strength, metal, institution-type wash basin and toilet. The wash basin and toilet may be combined in one unit. The wash basin shall have hot and cold running water.
    3. Detention strength light fixtures that provide at least 30 foot candles at 30 inches above the floor. Lights shall have a dimming capability or there shall be a nightlight to allow for comfortable sleeping. There shall be enough illumination for observation of juveniles during security checks.
    4. A minimum floor area of 35 square feet of unencumbered space. The distance between the floor and ceiling may not be less than 8 feet and the distance between opposite walls may not be less than 6 feet.
    (c) Receiving cells are not included in determining the rated capacity of a facility.
    (d) Juveniles may not be held in a receiving cell for more than 72 continuous hours.
    (7) Natural lighting. Cells under sub. (2) and s. DOC 346.15 and dormitories under sub. (3) shall be provided with natural light in accordance with the International Building Code, s. 1204 as adopted by the department of safety and professional services under s. SPS 361.05 (1) . Artificial light may not be used as an alternative to the natural light requirements under the International Building Code.
    (8) Exterior windows.
    (a) This subsection applies to all windows that lead to the exterior of the facility or to an area outside the secure perimeter of the facility.
    (b) All exterior windows shall be translucent or shall be located to prevent persons outside the secure perimeter of the facility from observing juveniles within the facility.
    (c) Each exterior window that has an opening in any direction in excess of 5 ½ inches shall be covered with security steel grills to prevent escape.
    (d) If an exterior window is accessible to juveniles and opens, the window shall be mounted in a detention strength frame and shall be covered on the inside with a 1,600 pound per lineal inch tensile strength security screen of .047 mil. wire diameter to prevent the passage of contraband.
    (e) If an exterior window is not accessible to juveniles and opens, the screen shall have a tensile strength of at least 800 pounds per lineal inch and shall be made of wire of at least .028 mil. diameter.
    (f) If an exterior window does not open, whether or not it is accessible to juveniles, the security screen required under par. (d) or (e) may be omitted if the window is mounted in a detention strength frame and the pane is security glass of sufficient strength to resist breakage and prevent the passage of contraband.
    (9) Showers. There shall be at least one shower for every 8 juveniles. There shall be an adequate supply of hot and cold water so that juveniles shall be permitted to shower on a daily basis.
    (10) Multi-purpose space. Facilities shall contain multi-purpose space which shall have a minimum of 300 square feet of floor area or provide 35 square feet of floor area for the maximum number of juveniles expected to use the space at one time, whichever is greater.
    (11) Classroom space. For juvenile detention facilities which are constructed or substantially remodeled after November 1, 2010, there shall be classroom space designed in conformity with local or state educational requirements.
    (12) Health care area. If medical or dental services are provided in the facility, there shall be sufficient space, equipment, supplies and materials for the performance of primary health care delivery in a confidential and private manner. The superintendent shall consult with the health care provider to determine the adequacy of the space, equipment, supplies and materials.
    (13) Outdoor recreation space.
    (a) If provided, there shall be a minimum of 70 square feet of outdoor recreational space per occupant.
    (b) The operational plan under s. DOC 346.04 shall contain policies and procedures for the safe and secure use of outdoor recreational space.
    (14) Storage space.
    (a) Sufficient space shall be provided in the facility to store and issue clothing, bedding, cleaning supplies and other items for daily operations.
    (b) Space shall be provided for storing the personal property of juveniles safely and securely.
    (15) Visiting space. Sufficient space for visitation shall be provided.
History: CR 09-039 : cr. Register October 2010 No. 658 , eff. 11-1-10; correction to numbering of (2) (c) 6. made under s. 13.92 (4) (b) 1. , Stats., Register October 2010 No. 658 ; correction in (7) made under s. 13.92 (4) (b) 6. , 7. , Stats., Register January 2012 No. 673 .